23
Terminal block diagram
Warning!
High touch current earth connection essential before connecting supply.
2.If UPS rectier input and bypass input are supplied from one mains only:
Connect the mains supply cables to the UPS rectier input terminals L1, L2, L3, N and PE .
The following three jumpers must be xed between the rectier and bypass input terminals:
L1-L1, L2- L 2, L3- L3.